item:
English
  • sales@castlesecuritysystems.com
  • Customer

RE-9032-32 Zone Fire Alarm Control panel

₹   View price ?

Supply of 32 Zone Fire Alarm Control panel, with Touch key pad, 20 X 4 Charater LCD Display, Inbuild RS-485 Communiction card can connect Max. 16 panels in a single network communication, Peer to Peer network through RS-485 communication Approval: CE Mark. Optionals: 1) Provision to connect zone wise sounder (RE-90ZS) in a seperate cabinet. 2) Provision to connect zone wise relay (RE- 90ZC) in a seperate Cabinet 3) MODBUS Converter (RE-90MB) 4) TCP/IP Module (RE-TCP) 5) SOFT CONNECT software for PC Monitoring 6) Repeater Panel compatible with RE-900 RP Series for monitoring main panels. 7) provision to connect & integrate Conventional Public Adress system through RS-485 Communication (REVAC).

  • Availability Yes
  • Share on

Videos

Products Specification

Features:

 

20 X 4 Dot Matrix LCD display.

Alphanumeric keypads.

RS 485 Communication for Network Repeater.

System ON, AC ON, Battery ON, Charger ON indications.

Lamp test facility.

Maximum 16 panels including repeater can be connected in a Single Network via RS-485.

Repeater Panel can monitor the status of RE-900 series panels via RS-485 Network communication.

User can Disable / Enable the Zone of Fire Alarm Control Panel Connected in network.

Ravel Indian Manufacturer, International standard.

Operates on RS-485 communication.

Repeats all the parameters of the main FACP.

Electrical Specification

AC Power :

120-220 VAC,60/ 50 Hz

 

Battery (Lead Acid only)

Charging Current: Constant Voltage – 27.6v @ 0.5A (Max.).

24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery)

System Quiescent Current: 70mA

 

Operating Condition

Operating Temperature : 0 – 49° C / 32-120° F.

Relative Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ± 3° F.

 

Notification Appliance Circuits (Sounder Circuit)

Operating Nominal Voltage: 24 VDC

Sounder (NAC) output: 0.5A

End-Of-Line Resistor: 4.7K, 1/4watt

 

Potential Free Relay Contact

Type : Form C

No of Relays : 1

Relay Contact Rating: 2 Amps @ 30 VDC,

0.5 Amps @125 VAC,

Battery (Lead Acid only)

Charging Current: Constant Voltage – 27.6v @ 0.5A (Max.).

24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery)

System Quiescent Current: 70mA

 

 

 

Mechanical Specification

Dimensions : (350W X 300H X 100D)

Color : White

Construction : 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish

IP Rating : IP50

Cable Entry : 11xø19mm Knockout in top of the cabinet

 

 

Compatible Devices

Models Description

RE-900 series Fire Alarm Control Panel

 

 

Ordering Information

Model Description

Up to 32 Zones RE- 9032RP

Up to 128 Zones RE- 9128RP

Up to 256 Zones RE-9256RP

NOTE:

RE-9XXXRP →RE-900RP Series Repeater Panel

XXX → 32Zone , 128Zone, 256Zone