item:
English
  • sales@castlesecuritysystems.com
  • Customer

RE-104-4 Zone standalone Fire Alarm control Panel

₹   View price ?

Product Overview RE-104 is a right blend of affordable design and quality with latest technology for fire alarm control panels. This microprocessor based conventional Fire Alarm Control panel, is designed for small size commercial buildings and small scale industries. RE-104 model is an user friendly 4 zone standalone control panel, with optional zone wise Sounder/Contact respectively.


Videos

Products Specification

Ravel Indian Manufacturer, International standard.

Switch Mode Power Supply.

Modular Construction, Serviceable.

Surface Mount Technology.

Battery polarity & deep discharge protection.

As per IS -15908: 2011 Standard.

16 X 2 Dot Matrix LCD Display.

Standby battery backup with built in charging.

Fire / Fault status in unambiguous colored LED indication.

Switch Mode Power Supply.

Tactile Keypad for easy panel operation.

System on indication.

Main, Standby status indication.

Low Battery visual warning with audible tone.

Relay output for actuators for Fire and Fault.

Lamp Test facility

Zone wise one man walk Test Facility.

Zone wise Isolation facility with loop voltage cut off.

Compatible to all type of Conventional Detectors.

Optional Zone Wise Sounder / Zone Wise Contact.

Electrical Specification

Primary Power

120 – 220VAC , 50 Hz Common Relays

Type   :   Form C

No of Relays   :   3

Relay Contact Rating   :   2Amps @ 30 VDC, 0.5Amps @125VAC.

Power Factor   :   1

Standby Power

24V D.C (2 Nos of 12v, 7Ah Sealed Lead acid battery).

Quiescent current   :   55mA  

Operating Condition

Operating Temperature   :   0 – 49° C/32-120° F.

Relative Humidity   :   93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F. Initiating Device Circuits (Zone Circuit)

All zones are Class B wiring

Normal Operating Voltage   :   14- 21 VDC

Alarm Current   :   15 – 30mA

Short Circuit Current   :   42mA Maximum

Loop resistance   :   50 ohms Maximum

End-Of-Line Resistor   :   4.7K, 1/4watt

Standby Current   :   6.8mA (2.4mA for Detectors)

Charging Circuit

Charging Voltage 28.2V, ±0.5V

Charging Current 0.5 A (Max.).  

Notification Appliance Circuits

Class B wiring

Operating Nominal Voltage   :   24VDC

Current for NACs   :   0.6 Amp

End-Of-Line Resistor   :   4K7, 1/4 watt  

 

 

Mechanical Specification

Dimensions : (350W X 250H X 100D)

Color : Red / White

Construction : 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish

IP Rating : IP50

Cable Entry : 11xø19mm Knockout in top of the cabinet

 

 

Ordering Information

Model Description

RE-104-R 4 ZONE Fire Alarm Panel

RE-104-W 4 ZONE Fire Alarm Panel

Note:

R- Red Color, W-White Color

 

Compatible Devices

Model Description

RE-316S-2L Photoelectric Smoke detector with base.

RE-316H-2L Heat detector with base.

RE-316SH-2L Photoelectric & Heat detector with base